Diesel generator set manufacturer

Production and sales of Cummins, Yuchai, Weichai, Shangchai

中文版

English

Tel:

+86 15366907266

Application

Your current location: Home >> Application

Bank finance

Author: Diesel generator manufacturer time: 2022-01-11

Demand and challenge of bank financial diesel generator set products

It is similar to the diesel generator set used in hospitals, but banks have higher requirements on anti-interference and other environmental aspects, so they have strict requirements on the performance stability, AMF and ATS functions, instantaneous start-up time, low noise, low exhaust emissions, anti-interference and other aspects of diesel generator sets.

1. Working conditions

The unit can work reliably and output power under the following conditions, and can work continuously for 24 hours in rated power output mode (including 10% overload for 1 hour every 12 hours);

The altitude does not exceed 1000 meters;

The lower limit of ambient temperature is-15 C and the upper limit is 40 C. Other environmental units can be selected.

2. Low working noise and low emission

Ultra-low noise, with enough quiet environment to ensure the data system and bank staff to work with peace of mind;

Low exhaust emissions to ensure the cleanliness of the computer room and ensure the computer system and data.

3, the main and necessary protection device

The unit can automatically detect and alarm the starting battery voltage, and automatically delay the shutdown under the following conditions: too low, too high water temperature, too low water level, overload and startup failure, and send out corresponding signals;

Emergency stop under the following conditions: overspeed, short circuit, lack of phase, high voltage, voltage loss and low frequency;

Automatically send out audible and visual alarm signals under the following conditions: too low oil pressure, too high water temperature, too low water level, overload, startup failure, overspeed, short circuit, lack of phase, too high voltage, voltage loss, low frequency, too low startup battery voltage, too high startup battery voltage, low oil level and relay contacts in the alarm system of the unit;

The starting mode of the unit is selected as automatic starting mode. The unit must have AMF (automatic mains failure) function and be equipped with ATS to realize full automatic starting. When the mains power fails, the starting time is delayed : After 5 seconds (adjustable), the unit can be started automatically (there are three consecutive automatic starting functions), and the full negative switching time of the mains/unit is ; 10 seconds, the time required to fully meet the input load is less than 12 seconds. After the commercial power is restored, the unit will stop automatically after maintaining 0-300 seconds of operation and cooling (adjustable);

Equipped with UPS power supply system.

4. The brushless permanent magnet excitation alternator can provide high motor starting endurance, and has anti-interference to the waveform distortion of the output voltage of the main stator caused by nonlinear load, which can improve the generator's capacity with nonlinear load. Stronger ability to withstand short-circuit current (usually up to 3 times the rated current for 10S).

5, stable performance and strong reliability

The average time between failures of the unit is not less than 2000 hours;

In terms of technical performance, the no-load voltage setting range of the unit is 95-105 rated voltage;

When the unit supplies power to the phase-controlled rectifier, switching power supply, UPS power supply or other loads, low-frequency oscillation will not occur when the starting load is less than the rated value of unit 50.

The generator can overload 1.5 times the rated current at rated voltage for 2 minutes;

The unit has the functions of telemetry, remote communication and remote control, and can monitor, collect, process, record and report the relevant data of the equipment locally and remotely.

 

solutions

The generator set with excellent and stable performance is designed with low noise and equipped with PLC-5220 control system with AMF function. By connecting with ATS, it is ensured that the bank can provide power immediately once the main power supply is cut off. Stable, low noise, engine power meeting European and American emission standards, AMF function and ATS equipment meet the special requirements of banks. Equipped with RS232 or RS485/422 communication interface, it can be connected with a computer for remote monitoring, remote control, remote communication and telemetry, and it can be fully automatic and unattended.

 

advantages

Provide a complete set of products and solutions, reduce the user's requirements for mastering technology, and make the use and maintenance of the unit easier;

The control system has AMF function, which can be started automatically, and has many automatic stop and alarm functions under monitoring;

Optional ATS, small units can choose built-in ATS;

Ultra-low noise power generation to meet the needs of daily life;

Stable performance, the average time between failures of the unit is not less than 2000 hours;

The unit is small in size, and some devices can be selected to meet the operation requirements in cold areas and high temperature areas;

The special needs of some customers can be customized for design and development.







One-button dialing Contact